![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3fv/sysdrive-3g3fv_user-manual_743234128.webp)
5-6
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
H3-08
Term 14 Signal
0 to 2
---
2
Advanced
Terminal 14 Signal Level Settings
Setting
Name
Function
0
0 to 10 VDC
0 to 10 VDC input
1
–10 to 10 VDC
–10 to 10 VDC input
(A negative voltage is a command for rotation in the opposite direction.)
2
4 to 20 mA
4 to 20 mA input
Note When the terminal is being used as a voltage input terminal (setting 0 or 1), jumper J1 must be
disconnected on the control board. (See the following diagram.) The terminal’s input resistor will
be destroyed if the terminal is used for a voltage input with jumper J1 connected.
•
When frequency references are being input simultaneously from both the voltage terminal 13 and the
current terminal 14, the final reference value will be the sum of the two references that are input.
•
To switch the frequency reference input between the voltage terminal 13 and the current terminal 14,
set a value of 1F in any one of the multi-function inputs (H1-01 through H1-06). The voltage terminal 13
will be used when this multi-function input is OFF and the current terminal 14 will be used when this
multi-function input is ON.
•
The following diagram shows the location of jumper J1 on a 200-V Class, 0.4-kW Unit.
Jumper wire
Control
circuit
terminals
Main circuit
terminals
H
Frequency Reference: Terminal 16 Voltage Input (H3-04 and H3-05)
This function is useful when switching between two analog inputs. When using this multi-function input
(terminal 16) as the frequency reference terminal, first set the multi-function analog input’s function to
“Auxiliary Reference” by setting parameter H3-05 to “0.” (Neither H3-04 nor H3-05 can be changed dur-
ing operation.)
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...