D
Inverter Operating 1 (“During RUN 1,” Setting: 0)
OFF
The run command is OFF and there is not output voltage.
ON
The run command is ON and voltage is being output.
D
Inverter Operating 2 (“During RUN 2,” Setting: 37)
OFF
The Inverter is not outputting a frequency. (Baseblock, DC braking, initial excitation, or stopped)
ON
The Inverter is outputting a frequency.
•
These outputs can be used to indicate the Inverter’s operating status.
Output frequency
Run command
Baseblock command
During RUN 1 output
During RUN 2 output
ON
ON
OFF
OFF
ON
OFF
ON
OFF
D
Excitation (Setting: 1)
OFF
The output frequency is greater than the minimum output frequency (E1-09).
(With flux vector control, the output frequency is greater than the excitation level (b2-01).)
ON
The output frequency is less than the minimum output frequency (E1-09).
(With flux vector control, the output frequency is less than the excitation level (b2-01).)
Minimum output frequency (E1-09)
(Excitation level (b2-01) when flux vector control is being used.)
Output frequency
Excitation output
ON
OFF
D
Overload OL1 (Setting: 1F)
OFF
The motor protection function’s electronic thermal value is less than 90% of the detection level.
ON
The motor protection function’s electronic thermal value is greater than 90% of the detection level.
•
This output function is valid when the motor overload protection function is enabled (L1-01 =1).
•
This output can be used to warn of overheating before the protection function itself operates.
D
OH Prealarm (Setting: 20)
OFF
The cooling fin temperature is less than the “OH Pre-Alarm Level” set in L8-02.
ON
The cooling fin temperature exceeds the “OH Pre-Alarm Level” set in L8-02.
•
This output function indicates that the temperature of the cooling fins reaches the temperature set in
L8-02 (the Inverter overheating alarm detection level).
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...