7-33
Para
meter
No.
Page
Control mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Name
Para
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
F4-01
Channel 1
output
monitor
selection
Effective when an Analog
Monitor Card is used.
Monitor selection: Set the
number of the monitor item to
1 to 38
2
NO
B
B
B
B
6-73
AO Ch1
Select
number of the monitor item to
be output. (U1-
)
Gain: Set the multiple of 10 V
f
t
tti
it
it
F4-02
Channel 1
gain
for outputting monitor items.
Note: 4, 10, 11, 12, 13, 14, 25,
28 cannot be set 29 to 31
0.00 to
2.50
1.00
OK
B
B
B
B
6-73
AO Ch1
Gain
28 cannot be set. 29 to 31
are not used. When the
3G3IV-PAO12 is used
F4-03
Channel 2
output
monitor
selection
3G3IV-PAO12 is used
outputs of
±
10 V are pos-
sible. In this case, set
H4-07 (select multi-func-
tion analog output signal
level) to 1 When the
1 to 38
3
NO
B
B
B
B
6-73
AO Ch2
Select
g
g
level) to 1. When the
3G3IV-PAO08 is used,
only outputs of 0 to 10 V
F4-04
Channel 2
gain
only out uts of 0 to 10 V
are possible.
0.00 to
2.50
0.50
OK
B
B
B
B
6-73
AO Ch2
Gain
F4-05
Channel 1
output
monitor
bias
Sets the bias value of channel 1
on the Analog Monitor Card. Set
as a percentage with 10 V
equivalent to 100%.
–10.0
to 10.0
0.0
OK
B
B
B
B
6-73
AO Ch1
Bias
q
F4-06
Channel 2
output
monitor
bias
Sets the bias value of channel 2
on the Analog Monitor Card. Set
as a percentage with 10 V
equivalent to 100%.
–10.0
to 10.0
0.0
OK
B
B
B
B
6-73
AO Ch2
Bias
q
F5-01
Channel 1
output
selection
Selects the function to be set for
channel 1 when a Contact
Output Card is used. The same
functions can be set as for
0 to 37
0
NO
B
B
B
B
---
D0-02 Ch1
Select
functions can be set as for
multi-function outputs H2-01 to
H2-03.
F5-02
Channel 2
output
selection
Selects the function to be set for
channel 1 when a Contact
Output Card is used. The same
functions can be set as for
0 to 37
1
NO
B
B
B
B
---
D0-02 Ch2
Select
functions can be set as for
multi-function outputs H2-01 to
H2-03.
F6-01
Digital
output
selection
Selects the digital output
method for when a Digital
Output Card is used.
0, 1
0
NO
B
B
B
B
---
D0-08
Selection
0: 8 channels individually
1: Code output (binary code)
F7-01
Output
pulse
multiple
selection
Effective when a Pulse Monitor
Card is used. Sets the number
of output pulses.
0: 1F, 1: 6F, 2: 10F, 3: 12F, 4:
36F
Note: F= the output frequency
displayed in Hz.
0 to 4
1
NO
B
B
B
B
6-73
PO-36F
Selection
dis layed in Hz.
Example: When 0 (1F) is
set, and the output fre-
quency is 60 Hz, 60
pulses per second are
output. (50% duty)
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...