6-6
6-1-4 Setting Magnetic Flux Characteristics for Open-loop
Vector Control
Set the following parameter to select the method for V/f calculation to determine the magnetic flux char-
acteristics. The default setting does not normally need to be changed. Set the parameter if stable slip
compensation is required in the constant output area where the operating frequency is as high as or
higher than the rated frequency.
Parameter
Display
Setting
Units
Default
Valid access levels
number
p y
name
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C3-05
Flux Se-
lect
0, 1
---
0
---
Advanced
---
Settings
Setting
Description
0
The calculation of magnetic flux in open-loop vector control is based on the output frequency after
slip compensation.
1
The calculation of magnetic flux in open-loop vector control is based on the output frequency with
the V/f characteristic (i.e., the value without slip compensation).
Note Set the parameter to 1 if the speed of the motor is unstable in the constant output area.
6-1-5 Operation for Saturated Output Voltage
Previously, the accuracy of motor speed for vector control was greatly reduced when the
limit of the Inverter’s voltage output was approached (a voltage greater than that of the
input power supply cannot be output).
Set the following parameter to control the output voltage so that the limit will not be
reached, thus maintaining speed accuracy.
Parameter
Display
Setting
Units
Default
Valid access levels
number
p y
name
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C3-06
Output V
limit
0, 1
---
0
---
Advanced
---
Settings
Setting
Description
0
Disabled. (There is no limit of output voltage saturation. Slip compensation is disabled when the
output voltage saturates.)
1
Enabled. (Output voltage saturation is suppressed to maintain speed control.)
Note 1. Set the parameter to 1 if accuracy of speed is required within the rated rpm range. This will
cause an increase of approximately 10% in the output current. Therefore, be sure that Invert-
er has more than sufficient output current.
Note 2. If the Inverter’s input voltage is extremely lower than the rated motor voltage, the accuracy of
the speed of the motor may not be maintained even with the output voltage suppressed.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...