8-10
Minor fault display
Probable causes and remedies
Meaning
DEV (flashing)
Speed Deviation
The speed deviation has been
greater than the setting in
F1-10 for longer than the
setting in F1-11.
•
The load is too large.
→
Lighten the load.
•
The acceleration time and deceleration time are
too short.
→
Lengthen the acceleration time and decelera-
tion time.
•
The load is locked.
→
Check the mechanical system.
•
The settings in F1-10 and F1-11 aren’t appropriate.
→
Check the settings in F1-10 and F1-11.
•
The torque limit is set to 0 through CompoBus/D
communications. (Applies only to flux vector con-
trol.)
→
Set F9-05 to 0 (torque limit disabled).
EFO
Opt External Flt
External fault
(Communications/option)
•
An external fault was input from an Optional Com-
munications Card.
→
Reset the external fault from the Optional Com-
munications Card.
→
Remove the cause of the external fault input.
EF3 (flashing)
External Fault 3
External fault (Input terminal 3)
•
An external fault was input from a multi-function in-
put.
EF4 (flashing)
External fault (Input terminal 4)
ut.
→
Reset external fault inputs to the multi-function
EF5 (flashing)
External fault (Input terminal 5)
→
Reset external fault in uts to the multi-function
inputs.
EF6 (flashing)
External fault (Input terminal 6)
in uts.
→
Remove the cause of the external fault.
EF7 (flashing)
External fault (Input terminal 7)
→
Remove the cause of the external fault.
EF8 (flashing)
External fault (Input terminal 8)
CALL
SI-F/G ComCall
SYSMAC BUS CALL error
Only 00 was received since
communications were
established.
Only 00 was transmitted since communications
were established and the host was ready.
Note The Inverter waits for the host to be ready.
Clear this standby state by sending data.
→
Correct the program so that data other than 00
is sent first after communications are estab-
lished.
Maintenance Operations
Chapter 8
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...