6-105
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L4-05
Ref Loss Sel
0 or 1
---
0
Advanced
Note This parameter cannot be changed during operation.
Setting
Function
0
Stop. (Operate according to the frequency reference value.)
1
Continue operation at 80% speed. (Continue operation with a speed that is 80% of the
value when the frequency reference was lost.)
•
The frequency reference is considered lost when the frequency reference voltage drops by 90% for
more than 400 ms.
Advanced Operation
Chapter 6