7-53
Para
meter
No.
Page
Control mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Name
Para
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
o2-02
Stop Key
Sets the Stop Key in the run
mode.
0:
Disabled (When the run
command is issued from
0, 1
1
NO
B
B
B
B
6-112
Oper Stop
Key
command is issued from
and external terminal, the
Stop Key is disabled.)
1:
Enabled (Effective even
during run.)
o2-03
User
parameter
initial val-
ues
Clears or stores user initial
values.
0:
Stores/not set
1:
Begins storing (Records the
set parameters as user
initial values.)
2:
All clear (Clears all
recorded user initial values)
0 to 2
0
NO
B
B
B
B
6-112
User De-
faults
recorded user initial values)
Note: When the set parameters
are recorded as user ini-
tial values, 1110 will be
displayed in the Initialize
mode (A1-03.)
o2-04
Inverter ca-
pacity
selection
Do not set
Note: This parameter is set by
the manufacturer
0 to FF
(See
note.)
0 (See
note.)
NO
B
B
B
B
6-113
Inverter
Model #
the manufacturer
)
o2-05
Frequency
reference
setting
method
When the frequency reference
is set on the Digital Operator’s
frequency reference monitor,
sets whether the Enter Key is
necessary.
0:
Enter Key needed
1:
Enter Key not needed
0, 1
0
NO
A
A
A
A
6-113
Operator
M.O.P.
1:
Enter Key not needed
Note: When set to 1, the Invert-
er accepts the frequency
reference without Enter
Key operation.
o2-06
Operation
selection
when Digi-
tal Operator
is discon-
nected
Sets the operation when the
Digital Operator is
disconnected.
0:
Disabled (Operation
continues even if the Digital
Operator is disconnected.)
1:
Enabled (OPR is detected
at Digital Operator
0, 1
0
NO
A
A
A
A
6-113
Oper
Detection
at Digital Operator
disconnection. Inverter
output is cut off, and fault
contact is operated.)
o2-07
Cumulative
operation
time setting
Sets the cumulative operation
time in hour units.
Note: Operation time is calcu-
0 to
65535
0
NO
A
A
A
A
6-113
Elapsed
Time Set
Note: O eration time is calcu
lated from the set values.
o2-08
Cumulative
operation
time selec-
tion
0:
Cumulative time when the
Inverter power is on. (All
time while the Inverter
power is on is
accumulated.)
0, 1
0
NO
A
A
A
A
6-113
Elapsed
Time Run
accumulated.)
1:
Cumulative Inverter run
time. (Only Inverter output
time is accumulated.)
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...