6-90
H
Multi-function Output Settings (H2)
Setting
Function
Control mode
g
V/f
V/f
w/PG
Open-loop
Vector
Flux
Vector
0
During RUN 1
OK
OK
OK
OK
1
Zero-speed
OK
OK
OK
OK
2
Fref/Fout Agree 1 (Detection width in L4-02)
OK
OK
OK
OK
3
Fref/Set Agree 1 (Detection width in L4-02)
OK
OK
OK
OK
4
Frequency Detection 1 (–L4-01
≥
output frequency
≥
+L4-01)
OK
OK
OK
OK
5
Frequency Detection 2 (|Output frequency|
≥
L4-01)
OK
OK
OK
OK
6
Inverter Ready (Initialization completed, no faults)
OK
OK
OK
OK
7
DC Bus Undervoltage (Main circuit voltage too low)
OK
OK
OK
OK
8
Baseblock 1
OK
OK
OK
OK
9
Option Reference (ON: Frequency reference from Operator)
OK
OK
OK
OK
A
Remote Operation (ON: Run command from Operator)
OK
OK
OK
OK
B
Torque Detection 1 (N.O.)
OK
OK
OK
OK
C
Loss of Reference (Valid when L4-05 is set to 1.)
OK
OK
OK
OK
D
DB overheat (DC braking resistor overheating or faulty)
OK
OK
OK
OK
E
Fault (A fault other than CPF00 or CPF01 occurred.)
OK
OK
OK
OK
10
Minor Fault (Alarm display)
OK
OK
OK
OK
11
Reset Command Active (Fault reset command in progress)
OK
OK
OK
OK
12
Timer Output
OK
OK
OK
OK
13
Fref/Fout Agree 2 (Detection width in L4-04)
OK
OK
OK
OK
14
Fref/Set Agree 2 (Detection width in L4-04)
OK
OK
OK
OK
15
Frequency Detection 3 (Output frequency
≤
–L4-03)
OK
OK
OK
OK
16
Frequency Detection 4 (Output frequency
≥
–L4-03)
OK
OK
OK
OK
17
Torque Detection 1 (N.C.)
OK
OK
OK
OK
18
Torque Detection 2 (N.O.)
OK
OK
OK
OK
19
Torque Detection 2 (N.C.)
OK
OK
OK
OK
1A
Reverse Direction (Operating in reverse direction.)
OK
OK
OK
OK
1B
Baseblock 2
OK
OK
OK
OK
1C
Motor 2 Selected (ON: Motor 2 selected)
OK
OK
OK
OK
1D
Regenerating
---
---
---
OK
1E
Restart Enabled (Enabled during restart by Auto Restart
operation) (ON: During restart)
OK
OK
OK
OK
1F
Overload (OL1) (ON when 90% or more than detection level)
OK
OK
OK
OK
20
OH Prealarm (ON when temperature exceeds L8-02 setting)
OK
OK
OK
OK
30
Current/Torque Limit
---
---
OK
OK
31
Speed Limit
---
---
---
OK
33
Zero Servo End (Zero servo function completed)
---
---
---
OK
37
During RUN 2
(ON when outputting a frequency. OFF for baseblock,
DC braking, initial excitation, or stopped operation.)
OK
OK
OK
OK
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...