6-107
H
Fault Restart Settings (L5)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L5-01
Num of Restarts
0 to 10
---
0
Basic or Advanced
Note This parameter cannot be changed during operation.
Caution
The Inverter might be damaged when using the fault restart function.
Understanding that the Inverter might be damaged, be sure to take the following pre-
cautions:
Always set up a no-fuse breaker (NFB).
Set up a sequence that will stop peripheral equipment when an Inverter fault occurs.
•
The fault restart function automatically restarts the Inverter even when an internal fault occurs during
Inverter operation.
•
Use this function only when continuing operation is more important than damaging the Inverter.
•
The fault restart function is effective with the following faults. With other faults, the protective opera-
tions will engage immediately without attempting to restart operation.
OC (Over-current)
GF (Ground fault)
PUF (Fuse blown)
OV (Main circuit over-voltage)
UV1 (Main circuit under-voltage)
PF (Main circuit voltage fault)
LF (Output open-phase)
RF (Braking resistor overheated)
RR (Braking transistor failure)
OL1 (Motor overload)
OL2 (Inverter overload)
OL3 (Overtorque)
OL4 (Overtorque)
•
The fault restart count is cleared when operation is normal for 10 minutes after a fault restart is per-
formed or the power is turned off and then on again.
•
When one of the multi-function outputs (H2-01, H2-02, or H2-03) is set to 1E (Restart Enabled), the
output will be ON while the fault restart function is in progress.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L5-02
Restart Sel
0 or 1
---
0
Basic or Advanced
Note This parameter cannot be changed during operation.
Setting
Function
0
Do not output fault restart. (The fault contact does not operate.)
1
Output fault restart. (The fault contact operates.)
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...