6-64
6-5-4 Reference Parameters (d)
H
Setting the Frequency Reference Function (d2)
The frequency reference function sets the output frequency upper and lower limits.
When the frequency reference is zero and a run command is input, the motor operates at the frequency
reference lower limit (d2-02). The motor will not operate, however, if the lower limit is set lower than the
minimum output frequency (E1-09).
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
d2-01
Ref Upper Limit
0.0 to
110.0
%
100.0
Basic or Advanced
d2-02
Ref Lower Limit
0.0 to
109.0
%
0.0
Basic or Advanced
These parameters cannot be changed during operation.
Note The frequency reference upper and lower limits are set as a percentage of the maximum output
frequency (E1-04), in increments of 1%.
Internal frequency reference
Frequency reference upper limit (d2-01)
Frequency reference lower limit (d2-02)
Set frequency reference
H
Setting Prohibiting Frequency (Jump Frequencies) (d3)
This function allows the prohibition or “jumping” of certain frequencies within the Inverter’s output fre-
quency range so that the motor can operate without resonant vibrations caused by some machine sys-
tems. It is also used for deadband control.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
d3-01
Jump Freq 1
0.0 to
400.0
Hz
0.0
Basic or Advanced
d3-02
Jump Freq 2
0.0 to
400.0
Hz
0.0
Basic or Advanced
d3-03
Jump Freq 3
0.0 to
400.0
Hz
0.0
Basic or Advanced
d3-04
Jump Bandwidth
0.0 to
20.0
Hz
1.0
Basic or Advanced
These parameters cannot be changed during operation.
To disable this function, set the jump frequency references (d3-01 to d3-03) to 0.0 Hz.
For d3-01 to d3-03, set the center values of the frequencies to be jumped.
For d3-04, set the jump frequency bandwidth. The jump frequency
±
the jump bandwidth becomes the
jump frequency range.
Operation is prohibited within the jump frequency range, but changes during acceleration and decelera-
tion are smooth with no jumps.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...