8-1-3 Operation Errors
After the parameters have been set, an operation error will occur if there is an invalid
setting or a contradiction between two parameter settings.
It won’t be possible to start the Inverter until the parameters have been set correctly.
(The minor fault output and fault contact output will not operate, either.)
When an operation error has occurred, refer to the following table to identify and correct
the cause of the errors.
H
Operation Error Displays and Incorrect Settings
Display
Meaning
Incorrect settings
OPE01
kVA Selection
Incorrect Inverter
capacity setting
•
The Inverter capacity setting doesn’t match the Unit. (Contact
your OMRON representative.)
OPE02
Limit
Parameter setting
range error
•
The parameter setting is outside of the valid setting range.
OPE03
Terminal
Multi-function input
selection error
•
One of the following errors has been made in the multi-function
input (H1-01 to H1-06) settings:
•
The same setting has been selected for two or more multi-
function inputs.
•
An UP or DOWN command was selected independently.
(They must be used together.)
•
More than two out of the following four items are set.
UP/DOWN commands, Hold Accel/Decel, +Speed/–Speed
commands, and Sample/Hold for analog frequency refer-
ence.
•
Speed Search 1 (61) and Speed Search 2 (62) were selected
at the same time.
•
External Baseblock N.O. (8) and External Baseblock N.C. (9)
were selected at the same time.
•
The UP/DOWN commands (10 and 11) were selected while
PID control (b5-01) was enabled.
•
The Terminal 13/14 Switch (1F) was selected, but the terminal
14 function selector (H3-09) wasn’t set to frequency reference
(1F).
•
The +Speed and –Speed commands are not set at the same
time.
•
The NO and NC contacts of an emergency stop input are set at
the same time.
OPE05
Sequence Select
Optional Card
selection error
•
The Optional Card was selected as the frequency reference
source by setting b1-01 to 3, but an Optional Card isn’t con-
nected.
OPE06
PG Opt Missing
Control mode
selection error
•
V/f control with PG feedback was selected by setting A1-02 to 1,
but a PG Speed Control Card isn’t connected.
•
Flux vector control was selected by setting A1-02 to 3, but a PG
Speed Control Card isn’t connected.
Maintenance Operations
Chapter 8
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...