5-12
The acceleration time is the time required to go from 0% to 100% of the maximum frequency and the
deceleration time is the time required to go from 100% to 0% of the maximum frequency.
Four acceleration times and four deceleration times can be set. When using acceleration/deceleration
times 2 through 4, set “Multi-Accel/Decel 1” or “Multi-Accel/Decel 2” in the multi-function inputs (H1-01
through H1-06).
Parameter
Display name
Setting
S
Units Default
Valid access levels
number
p y
g
range (See
note 1.)
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C1-01
Acceleration time 1
0.0 to 6000.0
s
10.0
Quick-start, Basic, or Advanced
C1-02
Deceleration time 1 0.0 to 6000.0
s
10.0
Quick-start, Basic, or Advanced
C1-03
Acceleration time 2
0.0 to 6000.0
s
10.0
Basic or Advanced
C1-04
Deceleration time 2 0.0 to 6000.0
s
10.0
Basic or Advanced
C1-05
Acceleration time 3
0.0 to 6000.0
s
10.0
Advanced
C1-06
Deceleration time 3 0.0 to 6000.0
s
10.0
Advanced
C1-07
Acceleration time 4
0.0 to 6000.0
s
10.0
Advanced
C1-08
Deceleration time 4 0.0 to 6000.0
s
10.0
Advanced
Note 1. The setting range for the acceleration/deceleration times depends upon the setting in C1-10
(Acc/Dec Units). The table shows the setting range when the factory setting is used for C1-10.
If C1-10 is set to “0,” the setting range will be 0.00 to 600.00 s.
Note 2. Parameters C1-01 through C1-04 can be changed during operation, but C1-05 through
C1-08 cannot.
H
Emergency Stop Time Setting (C1-09)
Parameter C1-09 sets the deceleration time that will be used when an emergency stop signal is input or
a fault is detected; it can be changed during operation. The deceleration time is the time required to go
from 100% to 0% of the maximum frequency.
When using an emergency stop input, set a multi-function input (H1-01 through H1-06) to “Fast-Stop.”
The emergency stop time is effective for the following faults. Set a stopping method for each.
•
Inverter overheating (OH) pre-alarm: Set in L8-03.
•
Pulse generator faults: Set in F1-02 through F1-04.
Parameter
Display name
Setting
S
Units
Default
Valid access levels
number
p y
g
range (See
note.)
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C1-09
Fast Stop Time
0.0 to 6000.0
s
10.0
Basic or Advanced
Note The setting range for the emergency stop deceleration time depends upon the setting in C1-10
(Acc/Dec Units). The table shows the setting range when the factory setting is used for C1-10. If
C1-10 is set to “0,” the setting range will be 0.00 to 600.00 s.
H
Acceleration/Deceleration Time Switching Frequency (C1-11)
When the acceleration/deceleration time switching frequency is set in C1-11, the acceleration and de-
celeration times will be changed automatically as the frequency passes the set level. This parameter
cannot be changed during operation.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...