6-76
Setting
Description
Inverter’s status
Fault output
0
Deceleration 2: Decelerates to a stop
with C1-02 set.
Fault
ON
1
Coast to a stop.
Fault
ON
2
Emergency stop time: Decelerates to a
stop according to the C1-09 setting.
Fault
ON
3
Continuous operation. (See note.)
Alarm
OFF
Note If the parameter is set to 3, the Inverter will operates without references from the host controller.
Take necessary measures, such as emergency stop measures, to ensure safety.
Advanced Operation
Chapter 6