7-3
7-1
Initialize Mode Parameters
Para
meter
Name
Description
Setting
range
Default
setting
Chang
e d r
Control mode
Page
meter
No.
Display
name
range
setting
e dur-
ing
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
A1-00
Display
Language
Used to select the language
displayed on the Digital
Operator
0:
English
1:
Japanese
2:
German
3:
French
0 to 6
1
OK
Q
Q
Q
Q
3-18
Select
Language
3:
French
4:
Italian
5:
Spanish
6:
Portuguese
Note: This parameter is not ini-
tialized by the initialize
operation.
A1-01
Access
Level
Used to set the parameter
access level (set/read.)
0:
Monitoring only (Displays
only Operation mode and
Initialize mode)
1:
Used to select user
0 to 4
2
OK
Q
Q
Q
Q
3-18
Access
Level
1:
Used to select user
parameter
(Parameters A2-01 to A2-32
only can be set/read.)
2:
QUICK-START
3:
BASIC
4:
ADVANCED
A1-02
Select
Control
Method
Used to select the control
method for the Inverter
0:
V/f control
1:
V/f with PG
2:
Open loop vector
3
Fl
0 to 3
2
NO
Q
Q
Q
Q
3-19
Control
Method
O e
oo
ecto
3:
Flux vector
Note: This parameter is not ini-
tialized by the initialize
operation.
A1-03
Initialize
Used to initialize the parameters
using the specified method.
0:
No initializing
1110:
Initializes using the
0 to
3330
0
NO
Q
Q
Q
Q
3-20
Init
Parameters
1110:
Initializes using the
User parameters
2220:
Initializes using a
two-wire sequence.
3330:
Initializes using a
three-wire sequence.
A1-04
Password
When a password has been set
in A1-05 this function write
protects the password input
section of the Operation mode
parameter.
Note: If the password is
0 to
9999
0
NO
Q
Q
Q
Q
3-22
Enter
Password
Note: If the password is
changed, parameters
A1-01 to A1-03 and A2-01
to A2-32 can no longer be
changed. (Program mode
parameters can be
changed.)
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...