6-74
Explanation of Settings
Setting
Description
0
1F
1
6F
2
10F
3
12F
4
36F
Note “F” indicates the output frequency (Hz). For example, if “0” (1F) is set, when the output frequency
is 60 Hz there will be an output of 60 pulses per minute. (Duty 50%)
H
Setting a Wired SYSMAC BUS Interface Card (F8)
When using a 3G3IV-PSIG Wired SYSMAC BUS Interface Card, set the following parameter in order to
specify the operation of the Inverter for communications failures.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
F8-01
E-15 Det Sel
0 to 3
---
1
Basic or Advanced
Set the parameter according to the application.
Setting
Description
Inverter’s status
Fault output
0
Deceleration 2: Decelerates to a stop
with C1-02 set.
Fault
ON
1
Coast to a stop.
Fault
ON
2
Emergency stop time: Decelerates to a
stop according to the C1-09 setting.
Fault
ON
3
Continuous operation. (See note.)
Alarm
OFF
Note If the parameter is set to 3, the Inverter will operate without references from the host controller.
Take necessary measures, such as emergency stop measures, to ensure safety.
H
Setting a CompoBus/D Communications Card (F9)
When using a 3G3FV-PDRT1-SIN CompoBus/D Communications Card, make the communications
settings with the following parameters.
D
Setting Communications External Fault Input
Set the following three parameters to specify the detection method of communications external fault
input.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
F9-01
EF0 Selection
0, 1
---
0
Basic or Advanced
Explanation of Settings
Setting
Description
0
Normally open contact. (A communications external fault is input with the bit turns ON.)
1
Normally close contact. (A communications external fault is input with the bit turns OFF.)
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...