5-35
The timing of the initial excitation function depends on the zero-speed operation method selected with
b1-05, as shown in the following diagrams.
Run command
Frequency reference
from analog input
•
b1-05 = 1
(STOP)
•
b1-05 = 0
(RUN at Frequency Ref)
•
b1-05 = 2
(RUN at Min Frequency)
•
b1-05 = 3
(RUN at Zero RPM)
Initial excitation
BB
(Baseblock)
Initial excitation from E1-09
BB
Zero speed
Zero speed
Initial excitation
Inverter’s internal frequency reference
(Soft start input)
After the frequency reference falls below
E1-09, initial excitation starts when the
motor speed drops below b2-01.
After the run command goes OFF, initial
excitation starts when the motor speed
drops below b2-01.
After the run command goes OFF, initial
excitation starts when the motor speed
drops below b2-01.
Note 1. Initial excitation is started from b2-01 (excitation level) when decelerating.
A setting of b2-01 < E1-09 is valid only with flux vector control.
Note 2. The current level for the initial excitation function is set in E2-03 (no-load current). The DC
braking (injection) current (b2-02) isn’t used with flux vector control and can’t be set.
5-4-3 Auto-tuning
H
Inverter Input Voltage Setting (E1-01)
Set the Inverter’s input voltage (E1-01) to match the power supply voltage; it cannot be changed during
operation. This setting is used as the reference value for functions such as the protection functions.
Parameter
Display
Setting
Units
Default
Valid access levels
number
p y
name
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E1-01
Input Voltage
155 to 255
(310 to 510)
VAC
200
(400)
Quick-start, Basic, or Advanced
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...