5-2
This section explains the basic settings required to operate and stop the Inverter. The
parameter settings described here will be sufficient for simple Inverter operations.
After the basic settings common to all of the control modes are introduced, the basic set-
tings specific to each control mode will be explained. Read the common settings first and
then skip to the explanation for the control mode that will be used.
Even when your application requires special functions such as torque control or PID
control, make these basic settings first and then skip to the explanations of those special
functions. (Refer to
Chapter 6 Advanced Operation.)
5-1
Common Settings
5-1-1 Setting the Access Level and Control Mode
H
Setting the Access Level (A1-01)
Parameter A1-01 is used to select the parameter access level. This level determines which parameters
can be displayed and changed. This parameter can be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
A1-01
Access Level
0 to 4
---
2
Quick-start, Basic, or Advanced
Access Level Settings
The control mode setting also affects which parameters can be displayed and changed.
Setting
Name
Function
0
Operation Only This setting allows the operation mode and initialize mode to be displayed or
changed. Use this setting to prevent parameter settings from being changed.
1
User Level
This setting allows only the user-selected parameters (up to 32) to be displayed
or changed. Select the desired parameters as “User Parameters” in parameters
A2-01 through A2-32.
2
Quick-start
This setting allows the parameters required to start the Inverter (about 25) to be
displayed or changed.
3
Basic
This setting allows the commonly used parameters to be displayed or changed.
4
Advanced
This setting allows all parameters to be displayed or changed.
Note The parameters required for basic operation can be displayed and changed in the Basic level, but
this section also describes parameters that can be set only in the Advanced level, so set the ac-
cess level to Advanced.
Example
The following example shows how to change parameter A1-01 from Quick-start to Advanced.
Key sequence
Display
Explanation
** Main Menu **
Operation
Displays operation mode.
** Main Menu **
Initialize
Displays initialize mode.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...