3-20
Example
The following example shows how to change parameter A1-02 to select Flux Vector control (vector con-
trol with pulse generator).
Key sequence
Display
Explanation
** Main Menu **
Operation
Displays operation mode.
** Main Menu **
Initialize
Displays initialize mode.
Select Language
English
Puts the Unit in initialize mode.
(Select Language display)
2 times
Control Method
Open Loop Vector
Displays the Control Method display.
A1-02= 2
Open Loop Vector
Displays the parameter setting for A1-02.
A1=02 3
Flux Vector
Changes the setting to Flux Vector.
Entry Accepted
Writes the new setting.
Control Method
Flux Vector
Returns to the Control Method display.
S
Initializing the Parameters
Use parameter A1-03 to initialize the parameters. This parameter cannot be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f
with PG
Open Loop
Vector
Flux
Vector
A1-03
Init Parameters
0, 1110,
2220, or
3330
---
0
Quick-start, Basic, or Advanced
Initialize Parameters Settings
Setting
Function
0
Returns to the Initialize display without initializing any parameters.
1110
Initializes the parameters to the user settings.
This function initializes the parameters to values that have been recorded as user settings. To record
the user settings, change the parameters to the desired values and then set parameter o2-03 (User
Defaults) to 1. (The 1110 function is disabled when parameter o2-03 is 0.)
2220
2-wire sequential initialization (Initializes the parameters to the factory settings.)
3330
3-wire sequential initialization
H
Example of Wiring for 2-wire Sequential Operation
Forward rotation/Stop
11
Reverse rotation/Stop
Sequential input common
Preparing for Operation
Chapter 3
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...