6-13
Group
Control mode
Comments
Function
Group
Flux
Vector
Open-loop
Vector
V/f
w/PG
V/f
Comments
Function
Terminal
H1
Digital Inputs
Function selection for multi-function inputs
OK
OK
OK
OK
e
a
H2
Digital Outputs
Function selection for multi-function outputs
OK
OK
OK
OK
H3
Analog Inputs
Adjustment/function selection for external analog inputs
OK
OK
OK
OK
H4
Analog Outputs
Adjustment/function selection for multi-function analog
outputs
OK
OK
OK
OK
H5
Serial Com Setup
Not Used. (Do not change this setting.)
---
---
---
---
Protection
L1
Motor Overload
Sets electrical/thermal functions that protect the motor.
OK
OK
OK
OK
o ec o
L2
PwrLoss Ridethru
Selects the power-loss processing method.
OK
OK
OK
OK
L3
Stall Prevention
Accel/Decel/Run stall prevention settings and selection
OK
OK
OK
OK
L4
Ref Detection
Frequency detection settings and selection
OK
OK
OK
OK
L5
Fault Restart
Fault restart function settings
OK
OK
OK
OK
L6
Torque Detection
Sets overtorque detection functions 1 and 2 (by current)
OK
OK
OK
OK
L7
Torque Limit
Not used. (Can’t be set.)
---
---
OK
OK
L8
Hdwe Protection
Hardware overheating and phase loss protection settings
OK
OK
OK
OK
Operator
o1
Monitor Select
Selects the Operator’s display and setting methods.
OK
OK
OK
OK
O e a o
o2
Key Selections
Operator’s key function selection and other parameters
OK
OK
OK
OK
6-2-2 Energy-saving Control Function
The energy-saving control function is enabled when the energy-saving command (setting 63) has been
set in a multi-function input (H1-01 through H1-06). Inputting the energy-saving command while there is
a light load causes the Inverter’s output voltage to be reduced and saves energy. Turn OFF the energy-
saving command when a normal load is added.
Parameter b8-01 determines the Inverter’s output voltage when the energy-saving command is input.
Set this value as a percentage of the V/f pattern’s voltage. Parameter L2-04 (the voltage recovery time)
determines the rate at which the output voltage is changed when the energy-saving command is turned
ON or OFF.
Parameter b8-02 determines the lower limit frequency for the energy-saving function. The energy-sav-
ing command is enabled only when the frequency reference is above this lower-limit and the motor
speed is within the “speed agree” range.
Parameters b8-01 and b8-02 cannot be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b8-01
Energy Save Gain 0 to 100
%
80
Advanced
Not applicable.
b8-02
Energy Save Freq
0.0 to 400.0 Hz
0.0
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...