Increase the setting in C7-02 if vibration occurs when operating with a light load.
(If the setting is increased too much, the current can fall to the point where stalling occurs.)
•
Decrease the setting in C7-02 if stalling occurs.
•
Disable the hunting-prevention function (C7-01 = 0) if high responsiveness is more important than
suppressing vibration.
6-4-4 Setting Motor Parameters
The motor parameters other than the V/f pattern parameters are described below:
Calculate the rated slip (E2-02) from the value shown on the motor’s nameplate with the following equa-
tion and set this value.
Rated slip = rated frequency (Hz) – rated speed (r/min)
×
number of poles/120
Set the no-load current (E2-03) at the rated voltage and rated frequency. Normally this value isn’t shown
on the motor’s nameplate, so it might be necessary to contact the motor manufacturer.
Parameter
Display name
Setting range Units
Default
Valid access levels
number
p y
g
g
setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-02
Motor Rated Slip
0.00 to 20.00
Hz
2.90
Advanced
Quick Start, Basic,
E2-03
No-Load Current
0.00 to 2.90
(see note 2)
A
1.20
,
,
or Advanced
Note 1. The default setting depends upon the type of Inverter.
(The table shows the default settings for 200-V class, 0.4-kW Inverters.)
Note 2. The setting range is between 0.00 and 0.1 less than the Inverter’s rated current.
Note 3. These settings are used as reference values for the motor slip compensation function.
Set the motor’s terminal resistance (phase to phase) in parameter E2-05. Normally this value isn’t
shown on the motor’s nameplate, so it might be necessary to contact the motor manufacturer.
Parameter
Display name
Setting range
Units Default
Valid access levels
number
p y
g
g
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-05
Term Resistance 0.000 to 65.000
Ω
9.842
Advanced
Note 1. The default setting depends upon the type of Inverter.
(The table shows the default settings for 200-V class, 0.4-kW Inverters.)
Note 2. This setting is used as a reference value for the torque compensation function.
Parameter
Display name
Setting range Units
Default
Valid access levels
number
p y
g
g
setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-10
Tcomp Iron Loss
0 to 65535
W
14
Advanced
Not applicable.
Note 1. The default setting varies with the Inverter’s capacity. The above setting applies to 200-V
class, 0.4-kW Inverters.
Note 2. Set the iron core loss in 1-W increments. The default setting does not normally need to be
changed.
Note 3. The set value is used as the reference value for the torque compensation function.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...