7-42
H
Analog Outputs: H4
Para
meter
Name
Description
Setting
range
Default
setting
Chan-
ges
Control mode
Page
meter
No.
Display
name
range
setting
ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
H4-01
Multi-func-
tion analog
output 1
selection:
terminal 21
Sets the number of the monitor
item to be output (U1-
) from
terminal 21.
Note: Settings 4, 10, 11, 12, 13,
14, 25, 28, 34, and 35
1 to 38
2
NO
B
B
B
B
6-96
Terminal 21
Sel
14, 25, 28, 34, and 35
cannot be set and 29 to
31 are not used.
H4-02
Gain
terminal 21
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
0.00 to
2.50
1.00
OK
B
B
B
B
6-97
Terminal 21
Gain
Sets whether the monitor item
output will be output in multiples
of 10 V.
H4-03
Bias
terminal 21
Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic
–10.0
to
+10 0
0.0
OK
B
B
B
B
6-97
Terminal 21
Bias
Sets output characteristic
up/down parallel movement as
a percentage of 10 V.
+10.0
H4-04
Multi-func-
tion analog
output 2
selection:
terminal 23
Sets the number of the monitor
item to be output (U1-
) from
terminal 23.
Note: Settings 4, 10, 11, 12, 13,
14, 25, 28, 34, and 35
1 to 38
3
NO
B
B
B
B
6-96
Terminal 23
Sel
14, 25, 28, 34, and 35
cannot be set and 29 to
31 are not used.
H4-05
Gain
terminal 23
Sets the multi-function analog
output 2 voltage level gain.
Sets whether the monitor item
0.00 to
2.50
0.50
OK
B
B
B
B
6-97
Terminal 23
Gain
Sets whether the monitor item
output will be output in multiples
of 10 V.
H4-06
Bias
terminal 23
Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic
–10.0
to
+10 0
0.0
OK
B
B
B
B
6-97
Terminal 23
Bias
Sets output characteristic
up/down parallel movement as
a percentage of 10 V.
+10.0
H4-07
Analog
output
signal level
selection
Sets the signal output level for
multi-function outputs 1 and 2
(terminals 21, 23.)
0:
0 to +10 V output
1:
0 to
±
10 V output
0, 1
0
NO
B
B
B
B
6-97
AO Level
Select
1:
0 to
±
10 V out ut
Note: The optional Analog Mon-
itor Card may also be
used with this setting.
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...