7-14
Para
meter
No.
Page
Control mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Name
Para
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
C1-11
Accelera-
tion/decel-
eration
switching
frequency
Sets the frequency for automat-
ic acceleration/deceleration
switching.
Below set frequency: Accel/de-
cel time 4, above set frequency:
Accel/decel time 1
Note: The multi function input
0.0 to
400.0
0.0
NO
A
A
A
A
5-13
Acc/Dec
SW Freq
Note: The multi-function input
“multi-accel/decel time 1”
or “multi-accel/decel time
2” take priority.
Note The setting range for acceleration/deceleration times will differ according to the setting for C1-10
(the unit for acceleration/deceleration time.) When C1-10 is set to 0, the setting range for accel-
eration/deceleration times becomes 0.00 to 600.00 seconds.
H
S-curve Acceleration/Deceleration: C2
Para
meter
Name
Description
Setting
range
Default
setting
Chan-
ges
Control mode
Page
meter
No.
Display
name
range
setting
ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
C2-01
S-curve
characteris-
tic time at
accelera-
tion start.
Note: When the S-curve char-
acteristic time is set the
All sections of the S-curve
characteristic time are set in
seconds units.
0.00 to
2.50
0.20
NO
A
A
A
A
6-58
SCrv Acc
@ Start
acteristic time is set, the
accel/decel times will in-
crease by only half of
C2-02
S-curve
characteris-
tic time at
accelera-
tion end.
crease by only half of
the S-curve characteris-
tic times at start and
end.
Output frequency
0.00 to
2.50
0.20
NO
A
A
A
A
6-58
SCrv Acc
@ End
C2-03
S-curve
characteris-
tic time at
decelera-
tion start.
Time
0.00 to
2.50
0.20
NO
A
A
A
A
6-58
SCrv Dec
@ Start
C2-04
S-curve
characteris-
tic time at
decelera-
tion end.
0.00 to
2.50
0.00
NO
A
A
A
A
6-58
SCrv Dec
@ End
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...