6-110
•
This function detects changes in the main circuit’s DC voltage which indicate a power supply phase
loss, large imbalance in the power supply voltage, or deterioration of the main circuit condenser.
Setting
Function
0
Disabled.
1
Enabled. (Detects input power supply phase loss, 3-phase imbalance, or de
t
erioration of the
main circuit condenser.)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L8-07
Ph Loss Out Sel
0 or 1
---
0
Advanced
Note This parameter cannot be changed during operation.
•
This function detects an Inverter output phase loss.
Setting
Function
0
Disabled.
1
Enabled. (Detects an output phase loss at under 5% of the Inverter’s rated output current.)
•
False phase loss detections may occur when the motor’s capacity is small compared to the capacity of
the Inverter. In this case, disable the detection function by setting L8-07 to 0.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L8-10
Ground Fault Sel
0 or 1
---
1
Advanced
Settings
Setting
Function
0
Disabled. (No ground fault is protected.)
1
Enabled. (The ground fault is protected.)
•
The ground fault protective function can be enabled or disabled with the parameter.
•
The default setting does not normally need to be changed. Set the parameter to 0 if the output power
cable is as long as or longer than 100 m or the stray capacitance of the output cable is excessively high
and the ground fault protective function operates by mistake.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L8-17
L-Spd IGBD Prlcl
0 to 3
---
1
Advanced
Not ap-
plicable.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
L8-19
OL2 Chara@L-
Spd
0 or 1
---
0
Advanced
•
The inverter overload (OL2) characteristics can be set according to the application.
•
Set parameter L8-17 to 0 and parameter L8-10 to 1 if the motor has metal friction noise (or to increase
the carrier frequency).
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...