5-8
Set terminal 16’s gain and bias with H3-06 and H3-07. (Both settings can be changed during operation.)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
H3-06
Terminal 16 Gain
0.0 to
1,000.0
%
100.0
Basic or Advanced
H3-07
Terminal 16 Bias
–100.0
to 100.0
%
0.0
Basic or Advanced
Gain and Bias Chart
10 V
(20 mA)
0 V
(4 mA)
Frequency
reference
Max.frequency
Gain
100
Max.frequency
Bias
100
Note Use the current values shown in parentheses when current input has been selected.
The first-order lag’s digital filter can be set for all three analog inputs (frequency reference (voltage),
frequency reference (current), and multi-function analog input) with parameter H3-12. This setting is
effective when there are sudden changes or noise in the analog input signal. Responsiveness de-
creases as the setting increases.
The filter time constant cannot be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
H3-12
Filter Avg Time
0.00 to
2.00
s
0.00
Advanced
5-1-3 Frequency Reference Settings from Digital Operator
H
Selecting the Frequency Reference Source (b1-01)
Parameter b1-01 is used to select the reference source; it cannot be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b1-01
Reference Source
0 to 4
---
1
Quick-start, Basic, or Advanced
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...