6-73
The sign bit is used as a data bit, so only positive (plus) data can be set.
The second digit below the decimal point is set by bits 8x10
0
, 4x10
0
, and 2x10
0
, so the settings are
made in units of 0.02 Hz. (If these three bits are “111,” “110,” and “101,” they will be recognized as “9.”)
H
Setting an Analog Monitor Card (F4)
When using a 3G3IV-PAO08/PAO12 Analog Monitor Card, set the monitor items and gain with the fol-
lowing parameters. Parameters F4-02, F4-04, F4-05, and F4-06 can be changed during operation,
while F4-01 and F4-03 cannot.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
F4-01
AO Ch1 Select
0 to 38
---
2
Basic or Advanced
F4-02
AO Ch1 Gain
0.00 to
2.50
Multi-
ple
1.00
Basic or Advanced
F4-03
AO Ch2 Select
0 to 38
---
3
Basic or Advanced
F4-04
AO Ch2 Gain
0.00 to
2.50
Multi-
ple
0.50
Basic or Advanced
F4-05
AO Ch1 Bias
–10.0 to
10.0
%
0.0
Basic or Advanced
F4-06
AO Ch2 Bias
–10.0 to
10.0
%
0.0
Basic or Advanced
Set parameters F4-01 and F4-03 (AO Ch1 Select and AO Ch2 Select) to the right side of the of “U1”
parameters in the table on page 3-12 of this manual. The setting range is between 1 and 38, but the
following numbers cannot be set: 4, 10, 11, 13, 14, 25, 28, 29, 30, 31, 34, 35.
Set the parameters F4-05 and F4-06 (AO Ch1 Bias and AO Ch2 Bias) to a bias that moves the output
characteristics up and down in parallel in 1% increments based on 10 V as 100%.
When the 3G3IV-PAO12 is used, outputs of 0 to
±
10 V are possible. For that, set parameter H4-07 (mul-
ti-function analog output signal level selection) to “1” (0 to
±
10-V outputs). There are some monitor
items, however, that can only use outputs of 0 to +10 V even if parameter H4-07 is set to “1.”
When the 3G3IV-PAO08 is used, only outputs of 0 to +10 V are possible regardless of the parameter
H4-07 setting.
H
Setting a Pulse Monitor Card (F7)
When using a 3G3IV-PPO36F Pulse Monitor Card, set the number of output pulses with parameter
F7-01.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
F7-01
PO-36F
Selection
0 to 4
---
1
Basic or Advanced
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...