2-42
D
3G3FV-PPGX2 (For Flux Vector Control Mode Only)
Terminal
No.
Contents
Specifications
TA1
1
Power supply for pulse generator
12 VDC (
±
5%), 200 mA max. (see note)
2
y
g
0 VDC (GND for power supply)
3
5 VDC (
±
5%), 200 mA max. (see note)
4
A-phase + input terminal
Line driver input (RS-422 level input)
M
i
f
kH
5
A-phase – input terminal
(
)
Maximum response frequency: 300 kHz
6
B-phase + input terminal
7
B-phase – input terminal
8
Z-phase + input terminal
9
Z-phase – input terminal
10
Common terminal
0 VDC (GND for power supply)
TA2
1
A-phase + output terminal
Line driver output (RS-422 level output)
2
A-phase – output terminal
(
)
3
B-phase + output terminal
4
B-phase – output terminal
5
Z-phase + output terminal
6
Z-phase – output terminal
7
Control circuit common
Control circuit GND
TA3
(E)
---
Note 5 VDC and 12 VDC cannot be used at the same time.
Installation
Chapter 2
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...