6-46
H
Setting the Timer Function (b4)
The timer function is enabled when the timer function input (set value: 18) and the timer function output
(set value: 12) are set for the multi-function input and multi-function output respectively. These inputs
and outputs serve as general-purpose I/O. Chattering of sensors, switches, and so on, can be pre-
vented by setting a delay time.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b4-01
Delay-ON Timer
0.0 to
300.0
Sec
0.0
Advanced
b4-02
Delay-OFF Timer
0.0 to
300.0
Sec
0.0
Advanced
These parameters cannot be changed during operation.
•
When the timer function input ON time is longer than the value set for b4-01 (timer function ON-delay
time), the timer function output turns ON.
•
When the timer function input OFF time is longer than the value set for b4-02 (timer function OFF-
delay time), the timer function output turns OFF.
Operation Example
Timer function input
Timer function output
ON
ON
ON
ON
b4-01
b4-02
b4-01
b4-02
H
Setting PID Control (b5)
The PID control function is a control system that matches a feedback value (i.e., a de-
tected value) to the set target value. Combining proportional (P), integral (I), and deriva-
tive (D) control makes control possible even for a mechanical system with dead time.
The PID control provided by the SYSDRIVE 3G3FV Inverter is not suited for control that
requires a responsiveness of 50 ms or less.
This section explains the PID control applications and operations, along with the param-
eter settings and tuning procedure.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...