Presetting Frequency Reference Values (d1-01 through d1-09)
Parameters d1-01 through d1-08 contain preset reference values 1 through 8. The setting range for all
of the values is 0 to the max. frequency. These 8 parameters can be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
d1-01
Reference 1
0 to max.
o1-03
6.00 Hz
Quick-start, Basic, or Advanced
d1-02
Reference 2
0 to max.
o1-03
0.00 Hz
Quick-start, Basic, or Advanced
d1-03
Reference 3
0 to max.
o1-03
0.00 Hz
Quick-start, Basic, or Advanced
d1-04
Reference 4
0 to max.
o1-03
0.00 Hz
Quick-start, Basic, or Advanced
d1-05
Reference 5
0 to max.
o1-03
0.00 Hz
Basic or Advanced
d1-06
Reference 6
0 to max.
o1-03
0.00 Hz
Basic or Advanced
d1-07
Reference 7
0 to max.
o1-03
0.00 Hz
Basic or Advanced
d1-08
Reference 8
0 to max.
o1-03
0.00 Hz
Basic or Advanced
Note 1. The units for these values are set in o1-03.
Note 2. The frequency reference’s initial value and set value will change when o1-03 is changed.
For example, if preset reference 1 is set to 6.00 Hz and o1-03 is changed to 1 (0.01% units),
the setting for preset reference 1 will become 10.00%.
Note 3. When using preset references 2 through 8, be sure to set Multi-Step Reference 1, 2, and 3 in
the multi-function inputs (H1-01 through H1-06) as required.
When using the Jog function, set the jog frequency reference in parameter d1-09. The setting range for
this value is 0 to the max. frequency. This parameter can be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
d1-09
Jog Reference
0 to max.
o1-03
6.00 Hz
Quick-start, Basic, or Advanced
Note 1. When performing the Jog operation from an external terminal, set the multi-function inputs
(H1-01 through H1-06) to “Jog Frequency Reference,” “Forward Jog,” or “Reverse Jog” as
required.
Note 2. The multi-function input setting is unnecessary when performing the Jog operation from the
Operator.
5-1-4 Run Source and Responsiveness Settings
H
Selecting the Run Source (b1-02)
Parameter b1-02 is used to select the source of the run command; it cannot be changed during opera-
tion. When a control circuit terminal (external terminal) is set, the Unit operates with 2-wire forward/stop
and reverse/stop control. (When the Unit has been initialized for a 3-wire control or a multi-function input
is set to “0” (3-wire control), the Unit operates with 3-wire run, stop and forward/reverse control.)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b1-02
Run Source
0 to 4
---
1
Quick-start, Basic, or Advanced
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...