7-37
Setting
value
Page
Control mode
Function
Setting
value
Page
Flux
vector
Open loop
Vector
V/f
w/PG
V/f
Function
1D
Trim control decrease (ON: d4-02 frequencies are
subtracted from analog frequency references.)
OK
OK
OK
OK
6-84
1E
Sample/hold analog frequency reference (ON:
Hold analog value)
OK
OK
OK
OK
6-85
1F
Frequency reference terminal 13/14 selection
(ON: select terminal 14)
Valid only when H3-09 is set to “1F”.
OK
OK
OK
OK
5-19
20 to
2F
External fault (Desired settings possible)
Input mode: contact a/contact b,
Detection mode: Normal/during operation
Stopping method: Ramp to stop, coast to stop,
fast stop or continue operation.
OK
OK
OK
OK
6-86
30
Reset PID control integration (ON: resets the PID
control integration value)
OK
OK
OK
OK
6-54
31
Hold PID control integration (ON: maintains the
PID control integration value)
OK
OK
OK
OK
6-54
60
DC injection braking command (ON: DC
operation)
OK
OK
OK
OK
6-88
61
External speed search command 1: Maximum
frequency (ON: speed search)
OK
---
OK
---
6-88
62
External speed search command 2: Set frequency
(ON: speed search)
OK
---
OK
---
6-88
63
Energy save mode (ON: Energy-saving control
set for b8-01, b8-02)
OK
OK
---
---
6-13
64
External speed search command
OK
OK
OK
OK
---
65
KEB (deceleration operation for momentary
power interruption) command (NC contact)
OK
OK
OK
OK
---
66
KEB (deceleration operation for momentary
power interruption) command (NO contact)
OK
OK
OK
OK
---
71
Speed/torque control change (ON: Torque control) ---
---
---
OK
6-89
72
Zero-servo command (ON: Zero-servo lock)
---
---
---
OK
6-89
77
Speed control (ASR) proportional gain switch
(ON: C5-03)
---
---
---
OK
6-89
H
Digital Outputs: H2
Parame-
ter No
Name
Description
Setting
range
Default
setting
Chan-
ges
Control mode
Page
ter No.
Display
name
range
setting
ges
during
opera-
tion
V/f con-
trol
V/f with
PG
Open
loop
vector
Flux
vector
H2-01
Multi-func-
tion contact
output: ter-
minal 9 to
10.
Terminal 9 to 10 Sel
0 to 37
0
NO
B
B
B
B
6-91
H2-02
Multi-func-
tion output
1: terminal
25.
Terminal 25 Sel
0 to 37
1
NO
B
B
B
B
6-91
H2-03
Multi-func-
tion output
2: terminal
26.
Terminal 26 Sel
0 to 37
2
NO
B
B
B
B
6-91
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...