7-48
Para
meter
No.
Page
Control mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Name
Para
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
L4-05
Operation
when
frequency
reference is
lost
0: Stop (Operation follows the
frequency reference.)
1: Operation at 80% speed
continues. (At 80% of speed
before the frequency reference
was lost)
N t
F
f
i
0, 1
0
NO
A
A
A
A
6-105
Ref Loss
Sel
Note: Frequency reference is
lost: Frequency reference
dropped over 90% in
400 ms.
H
Fault Restart: L5
Para
meter
Name
Description
Setting
range
Default
setting
Chan-
ges
Control mode
Page
meter
No.
Display
name
range
setting
ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
L5-01
Number of
auto restart
attempts
Sets the number of auto restart
attempts. Automatically restarts
after a fault and conducts a
d
h f
th
0 to 10
0
NO
B
B
B
B
6-107
Num of
Restarts
speed search from the run
frequency.
L5-02
Auto restart
operation
selection
Sets whether a fault contact
output is activated during fault
restart.
0:
Not output (Fault contact is
not activated )
0, 1
0
NO
B
B
B
B
6-107
Restart Sel
not activated.)
1:
Output (Fault contact is
activated.)
H
Torque Detection: L6
Para
meter
Name
Description
Setting
range
Default
setting
Chan-
ges
Control mode
Page
meter
No.
Display
name
range
setting
ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
L6-01
Torque
detection
selection 1
0:
Overtorque detection
disabled.
1:
Detection during speed
agree only/Operation
continues after detection
(Minor fault)
2:
Detection during
run/Operation continues
after detection (Minor fault)
0 to 4
0
NO
B
B
B
B
6-108
Torq Det 1
Sel
after detection (Minor fault)
3:
Detection during speed
agree only/Inverter output is
shut off after detection
(Fault)
4:
Detection during
run/Inverter output is shut
off after detection (Fault)
L6-02
Torque
detection
level1
Vector control: Motor rated
torque is set as 100%.
V/f control: Inverter rated output
t i
t
100%
0 to
300
150
NO
B
B
B
B
6-108
Torq Det 1
Lvl
current is set as 100%.
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...