6-5
The following diagram shows the relationship between the output torque and each torque limit.
Output torque
Forward direction
Reverse direction
Forward
Reverse
Forward torque limit
Regenerative torque limit
Reverse torque limit
Regenerative torque limit
Note 1. When the forward torque limit has been set, the analog input signal acts as the limit value for
torque generated in the forward direction. The torque limit input is effective when torque is
generated in the forward direction even if the motor is operating in reverse (regenerative
torque).
Note 2. The torque limit is 100% of the motor’s rated torque when the analog input is at its maximum
value (10 V or 20 mA). To increase the torque limit above 100%, set the input terminal’s gain
above 100%. For example, a gain of 150.0% would result in a torque limit of 150% of the mo-
tor’s rated torque with a 10-V or 20-mA analog input.
6-1-3 Adjusting Speed Feedback
With open-loop vector control, internal Inverter data is used to calculate the feedback
value. The gain of this automatic frequency regulator (AFR) operation can be fine-tuned
according to motor response. (Normally it isn’t necessary to change the default setting.)
Parameter
Display
Setting
Units
Default
Valid access levels
number
p y
name
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C8-08
AFR Gain
0.00 to 10.00
Factor
1.00
---
Advanced
---
Parameter
Display
Setting
Units
Default
Valid access levels
number
p y
name
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C8-09
AFR Time
0 to 2000
ms
50
---
Advanced
---
Note 1. The default settings do not normally need to be changed.
Note 2. Fine-tune the gain or time constant if the rotation of the motor is unstable, causing hunting to
occur, or the torque and speed responsiveness of the motor is low.
Set parameter C8-09 to a larger value if hunting occurs. Set the parameter C8-08 to a smaller
value if hunting cannot be suppressed with the parameter C8-09.
Set parameter C8-09 to a smaller value within a range where no hunting occurs if the torque
and speed responsiveness of the motor are low. To increase the gain, set parameter C8-08 to a
larger value within a range where no hunting occurs.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...