3-19
Access Level Settings
Setting
Name
Function
0
Operation Only This setting allows operation mode and initialize mode to be displayed or
changed. Use this setting to prevent parameter settings from being changed.
1
User Level
This setting allows only the user-selected parameters (up to 32) to be displayed
or changed. Select the desired parameters as “User Parameters” in parameters
A2-01 through A2-32.
2
Quick-start
This setting allows the parameters required to start the Inverter (about 25) to be
displayed or changed.
3
Basic
This setting allows the commonly used parameters to be displayed or changed.
4
Advanced
This setting allows all parameters to be displayed or changed.
S
Setting the Control Mode
Use parameter A1-02 to select one of the four control modes. This parameter is not initialized by the
initialize operation and it cannot be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
A1-02
Control Method
0 to 3
---
2
Quick-start, Basic, or Advanced
Control Mode Settings
Setting
Name
Function
0
V/f Control
V/f control without pulse generator (normal V/f control)
1
V/f w/PG Fdbk
V/f control with pulse generator (V/f control using a PG Speed Control Card)
2
Open Loop Vector
Vector control without pulse generator
(Vector control using the Inverter’s internal speed information)
3
Flux Vector
Vector control with pulse generator
(Vector control using a PG Speed Control Card)
Control Mode Characteristics
Characteristic
V/f Control
V/f w/PG Fdbk
Open Loop Vector
Flux Vector
Basic control method
Voltage/frequency
control (open loop)
Voltage/frequency
control with speed
compensation
Current vector con-
trol without PG
Current vector con-
trol with PG
Speed detector
Not required
Required
(pulse generator)
Not required
Required
(pulse generator)
Optional Speed
Detectors
Not required
3G3FV-PPGA2 or
3G3FV-PPGD2
Not required
3G3FV-PPGB2 or
3G3FV-PPGX2
Speed control range
1:40
1:40
1:100
1:1,000
Starting torque
150%/3 Hz
150%/3 Hz
150%/1 Hz
150%/0 Hz
Speed control
precision
±
2 to 3%
±
0.03%
±
0.2%
±
0.02%
Torque limit
Not possible
Not possible
Possible
Possible
Torque control
Not possible
Not possible
Not possible
Possible
Example applications
•
Multiple motors
•
Simple speed
feedback control
•
Variable speed
drive applications
•
Simple servo
drives
•
Precision speed
control
•
Torque control
Preparing for Operation
Chapter 3
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...