5-3
Key sequence
Explanation
Display
Select Language
English
Puts the Unit in initialize mode.
(Select Language display)
Access Level
Quick Start
Displays the Access Level (A1-01).
A1-01= 2 ***
Quick-Start
Displays the parameter setting for A1-01.
2 times
A1-01= 4
Advanced
Changes the setting to Advanced.
Entry Accepted
Writes the new setting.
Access Level
Advanced Level
Returns to the Access Level display.
H
Setting the Control Mode (A1-02)
Parameter A1-02 is used to select one of the four control modes. This parameter is not initialized by the
initialize operation and it cannot be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
A1-02
Control Method
0 to 3
---
2
Quick-start, Basic, or Advanced
Control Mode Settings
Setting
Name
Function
0
V/f Control
V/f control without pulse generator (normal V/f control)
1
V/f w/PG Fdbk
V/f control with pulse generator (V/f control using a PG Speed Control Card)
2
Open Loop Vector
Vector control without pulse generator
(Vector control using the Inverter’s internal speed information)
3
Flux Vector
Vector control with pulse generator
(Vector control using a PG Speed Control Card)
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...