6-112
•
When the power is turned on, the frequency reference will appear in the Unit’s data display if the de-
fault settings are being used. Any one of the four values monitored at startup (frequency reference,
output frequency, output current, or the value set in parameter o1-01) can be selected to appear when
the power is turned on. The value that appears automatically at startup is determined by parameter
o1-02 (Power-On Monitor).
Setting
Name
Function
1
Frequency reference The frequency reference is displayed at start-up.
2
Output Frequency
The output frequency is displayed at start-up.
3
Output Current
The output current is displayed at start-up.
4
User Monitor
The value set in parameter o1-01 is displayed at start-up.
H
Key Function Settings/Other Settings (o2)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o2-01
Local/Remote Key 0, 1
---
1
Basic or Advanced
•
This parameter enables or disables the LOCAL/REMOTE Key (the Operation Mode Selector Key) on
the Digital Operator; it cannot be changed during operation.
Setting
Function
0
Disabled.
1
Enabled. (Pressing the LOCAL/REMOTE Key switches control of operation between the
Operator and the sources specified in parameters b1-01 and b1-02.)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o2-02
Oper Stop Key
0, 1
---
1
Basic or Advanced
•
This parameter enables or disables the STOP on the Digital Operator; it cannot be changed during
operation.
Setting
Function
0
Disabled. (The STOP Key is disabled when the run command is input from an external terminal.)
1
Enabled. (The STOP Key is enabled at all times during operation.)
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o2-03
User Defaults
0, 1, or 2
---
0
Basic or Advanced
•
This parameter is used to record or clear the user defaults; it cannot be changed during operation.
Once the user defaults have been recorded, parameter A1-03 can be used to initialize the Inverter’s
parameters to these defaults.
•
If the message “MAX Param Change” is displayed, the memory capacity is full. Reduce the number of
parameters that changed their default settings and register them again.
Note After the parameter o2-03 is set, the Digital Operator’s display will return to 0 when parameter
registration processing is completed.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...