3-12
S
Conditions for Monitoring
The following tables show the items that can be monitored in operation mode. The table’s “Valid access
levels” column indicates whether an item can be monitored in a particular access level and control
mode. The codes in this column have the following meanings.
Q: These items can be monitored in all access levels. (Quick-start, Basic, and Advanced)
B: These items can be monitored in the Basic and Advanced access levels.
A: These items can be monitored in the Advanced access level only.
X: These items cannot be monitored in the control mode shown.
The output signal levels for multi-function analog outputs shown in the table are for a gain of 100.0 and a
bias of 0.00.
Status Monitor
Item
Display
Function
Output signal
l
l f
Min.
U it
Valid access levels
e
sp ay
u c o
Ou pu s g a
levels for
multi-function
analog outputs
Units
V/f
V/f
w/PG
Open
Vec-
tor
Flux
Vec-
tor
U1-01
Frequency Ref
Monitors/sets the frequency reference
value.
The display units can be set with param-
eter o1-01.
10 V:
Max. frequency
(0 to
±
10 V possible)
0.01
Hz
Q
Q
Q
Q
U1-02
Output Freq
Monitors the output frequency.
The display units can be set with param-
eter o1-01.
10 V:
Max. frequency
(0 to
±
10 V possible)
0.01
Hz
Q
Q
Q
Q
U1-03
Output Current
Monitors the output current.
10 V: Rated current
(0 to +10 V output)
0.1 A
Q
Q
Q
Q
U1-04
Control Method
Shows which control mode is set.
Can’t be output.
---
Q
Q
Q
Q
U1-05
Motor Speed
Monitors the motor speed.
10 V:
Max. frequency
(0 to
±
10 V possible)
0.01
Hz
X
Q
Q
Q
U1-06
Output Voltage
Monitors the Inverter’s internal output
voltage reference value.
10 V: 200 (400) VAC
(0 to +10 V output)
0.1 V
Q
Q
Q
Q
U1-07
DC Bus Voltage
Monitors the DC voltage of the Inverter’s
internal main circuit.
10 V: 400 (800) VDC
(0 to +10 V output)
1 V
Q
Q
Q
Q
U1-08
Output kWatts
Monitors the output power. (This is an in-
ternally detected value.)
10 V:
Max. motor capacity
(0 to
±
10 V possible)
0.1
kW
Q
Q
Q
Q
U1-09
Torque Reference
Monitors the internal torque reference
value when vector control is used.
10 V: Rated torque
(0 to
±
10 V possible)
0.1%
X
X
Q
Q
U1-10
Input Term Sts
(Input terminal
status)
Shows the ON/OFF status of inputs.
U1-10=00000000
1: Terminal 1 ON
1: Terminal 2 ON
1: Terminal 3 ON
1: Terminal 4 ON
1: Terminal 5 ON
1: Terminal 6 ON
1: Terminal 7 ON
1: Terminal 8 ON
Can’t be output.
---
Q
Q
Q
Q
Preparing for Operation
Chapter 3
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...