4-10
•
Check the values on the motor nameplate and set each of the parameters.
E1-05 Maximum voltage (VMAX): Sets the motor rated voltage.
E1-06 Base frequency (FA): Sets the motor rated frequency.
E2-01 Motor rated FLA: Sets the motor rated current.
•
The setting procedure for these three parameters is as follows.
Key sequence
Display
Explanation
** Main Menu **
Operation
Displays operation mode.
2 times
** Main Menu **
Programming
Displays program mode.
Reference Source
Terminal
Puts the Unit in program mode.
14 times
Max Voltage
E1-05= 200.0 V
Press the Up Arrow Key to display the maximum
voltage. (see note)
Base Frequency
E1-06= 60.0 HZ
Displays the maximum voltage frequency. (see note)
5 times
Motor Rated FLA
E2-01= 1.90 A
Press the Up Arrow Key to display the rated current.
(see note)
** Main Menu **
Operation
Returns to the operation mode display.
Note When there are discrepancies between the displayed values and the rated values, set each value
separately.
4-2-6 No-load Operation
•
Operate the Digital Operator in with the motor in the no-load state (not connected to the mechanical
system).
H
Setting the Frequency Reference
•
Set the frequency reference on the frequency reference monitor in the operation mode.
•
The following is an operation example with the frequency reference set to 10 Hz.
Key sequence
Display
Explanation
** Main Menu **
Operation
Displays operation mode.
Frequency Ref
U1-01= 0.00 HZ
Puts the Unit in operation mode and displays the
frequency reference.
Frequency Ref
U1-01= 6.00 HZ
Switches operation to the Digital Operator. (SEQ, REF
and LED indicators turn OFF.)
Frequency Ref
006.00 HZ
Sets the frequency reference.
2 times
Frequency Ref
006.00 HZ
The first position flashes.
4 times
Frequency Ref
010.00 HZ
Set to 010.00 Hz.
Entry Accepted
The set values are overwritten.
Frequency Ref
010.00 HZ
Returns to the frequency reference display.
Trial Operation
Chapter 4
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...