6-32
Note 1. The setting units for parameters E1-04, E1-06, and E1-09 can be changed.
Note 2. This function is specific to flux vector control.
H
Setting Motor Parameters
The motor parameters (function E2) will all be set automatically when auto-tuning is performed, so it
normally isn’t necessary to set them manually. Set these parameters manually if auto-tuning can’t be
completed properly. These parameters cannot be changed during operation.
Set the rated current (A) shown on the motor’s nameplate.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-01
Motor Rated FLA
0.32 to 6.40
A
1.90
Quick Start, Basic, or Advanced
Note The setting range is 10% to 200% of the Inverter’s rated output current. The default setting de-
pends upon the type of Inverter. (The table shows the default setting for 200-V class, 0.4-kW In-
verters.)
Calculate the rated slip (E2-02) from the value shown on the motor’s nameplate with the following equa-
tion and set this value.
Rated slip = rated frequency (Hz) – rated speed (r/min)
×
number of poles/120
Set the no-load current (E2-03) at the rated voltage and rated frequency. Normally this value isn’t shown
on the motor’s nameplate, so it might be necessary to contact the motor manufacturer.
Parameter
Display name
Setting range Units
Default
Valid access levels
number
p y
g
g
setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-02
Motor Rated Slip
0.00 to 20.00
Hz
2.90
Advanced
Quick Start, Basic,
E2-03
No-Load Current
0.00 to 2.90
(see note 2)
A
1.20
,
,
or Advanced
Note 1. The default setting depends upon the type of Inverter.
(The table shows the default settings for 200-V class, 0.4-kW Inverters.)
Note 2. The setting range is between 0.00 and 0.1 less than the Inverter’s rated current.
Set the number of poles (E2-04) shown on the motor’s nameplate.
Parameter
Display name
Setting
Units
Default
Valid access levels*
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-04
Number of Poles
2 to 48
---
4
---
Q
---
Q
Note Q: Quick Start, Basic, or Advanced
---: Not applicable.
Set the motor’s terminal resistance between U and V, V and W, or W and U.
Usually the nameplate of the motor does not provide the motor’s terminal resistance. Contact the motor
manufacturer for a test report on the motor’s terminal resistance to set the following values.
•
Type E insulation:
Motor’s terminal resistance (
Ω
) at 75
°
C x 0.92
•
Type B insulation:
Motor’s terminal resistance (
Ω
) at 75
°
C x 0.92
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...