5-13
The “Multi-Accel/Decel 1” and “Multi-Accel/Decel 2” inputs will have priority when “Multi-Accel/Decel 1”
and “Multi-Accel/Decel 2” have been set in the multi-function inputs (H1-01 through H1-06).
Parameter
Display name
Setting
S
Units
Default
Valid access levels
number
p y
g
range (See
note.)
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
C1-11
Acc/Dec SW Freq
0.0 to 400.0
Hz
0.0
Advanced
Output
frequency
Acc/Dec Time Switching Frequency
(C1-11)
Acceleration/Deceleration Time 1 (C1-01 and C1-02) are used when the output frequency
≥
C1-11
Acceleration/Deceleration Time 4 (C1-07 and C1-08) are used when the output frequency < C1-11
5-1-6 Disabling Reverse Operation (b1-04)
Parameter b1-04 is used to enable and disable reverse command inputs. This parameter can be set to
“1” to disable reverse operation when necessary. This parameter cannot be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b1-04
Reverse Oper
0 or 1
---
0
Basic or Advanced
Settings
Setting
Name
Function
0
Reverse Enabled
Allows reverse operation.
1
Reverse Disabled
Prohibits reverse operation.
5-1-7 Selecting the Stopping Method (b1-03)
Parameter b1-03 sets the stopping method used when a stop command is input. This parameter cannot
be changed during operation.
Parameter
Display name
Setting
Units
Default
Valid access levels
number
p y
g
range
setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b1-03
Stopping Method
0 to 3
---
0
Quick-start, Basic, or Advanced
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...