7-35
Para
meter
No.
Page
Control mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Name
Para
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
F9-06
Operation
after
communica
tions error
Selects the inverter operation to
perform when a
communications (CompoBus/D
Communications Card) error
occurs.
0:
Decelerate to stop in the
time set in C1-02.
(Protective operation)
1:
Coast to stop
0 to 3
1
NO
B
B
B
B
6-75
BUS Fault
Sel
1:
Coast to stop.
(Protective operation)
2:
Emergency stop in the time
set in C1-09.
(Protective operation)
3:
Continue operation.
(Alarm)
7-2-6 Terminal Parameter Lists
H
Digital Inputs: H1
Parame-
ter No
Name
Description
Setting
range
Default
setting
Chan-
ges
Control mode
Page
ter No.
Display
name
range
setting
ges
during
opera-
tion
V/f con-
trol
V/f with
PG
Open
loop
vector
Flux
vector
H1-01
Multi-func-
tion input 1:
Terminal 3
selection
Terminal 3 Sel
0 to 77
24
NO
B
B
B
B
6-78
H1-02
Multi-func-
tion input 2:
Terminal 4
selection
Terminal 4 Sel
0 to 77
14
NO
B
B
B
B
6-78
H1-03
Multi-func-
tion input 3:
Terminal 5
selection
Terminal 5 Sel
0 to 77
3 (0)
(See
note.)
NO
B
B
B
B
6-78
H1-04
Multi-func-
tion input 4:
Terminal 6
selection
Terminal 6 Sel
0 to 77
4 (3)
(See
note.)
NO
B
B
B
B
6-78
H1-05
Multi-func-
tion input 5:
Terminal 7
selection
Terminal 7 Sel
0 to 77
6 (4)
(See
note.)
NO
B
B
B
B
6-78
H1-06
Multi-func-
tion input 6:
Terminal 8
selection
Terminal 8 Sel
0 to 77
8 (6)
(See
note.)
NO
B
B
B
B
6-78
Note The values in parentheses indicate initial values when initialized in 3-wire sequence.
D
Digital Input Functions List
Setting
l
Function
Control mode
Page
g
value
V/f
V/f
w/PG
Open loop
Vector
Flux
vector
g
0
3-wire control (Forward/Reverse command)
OK
OK
OK
OK
5-16
1
Local/Remote selection (ON: Operating, OFF:
Setting parameters)
OK
OK
OK
OK
6-79
Parameter Lists
Chapter 7
Summary of Contents for SYSDRIVE 3G3FV
Page 1: ...USER S MANUAL High function General purpose Inverter SYSDRIVE 3G3FV Cat No I516 E1 4 ...
Page 16: ...Chapter 1 Introduction 1 1 Function 1 2 Nomenclature 1 3 New Functions 1 ...
Page 33: ...Chapter 2 Installation 2 1 Mounting 2 2 Wiring 2 ...
Page 112: ...Chapter 4 Trial Operation 4 1 Procedure 4 2 Operation Example 4 ...
Page 289: ...Chapter 7 Parameter Lists 7 1 Initialize Mode Parameters 7 2 Program Mode Parameter List 7 ...
Page 366: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9 ...
Page 395: ...Chapter 10 Appendix 10 1 Notes on Using the Inverter for a Motor 10 ...