4-17
4 System Design
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
4-2 Wiring
4
4-2-2 Main Circuit and Li
near
Motor Con
nections
Terminal Block Specifications
*1
Do not short B1 and B2. Doing so may result in malfunctioning.
Precautions for Correct Use
Precautions for Correct Use
•
Tighten the frame ground screw to a torque of 1.4 to 1.6 N·m (M5).
•
Tighten the terminal block screws to a torque of 1.0 to 1.7 N·m (M5). Exceeding the maximum
allowable torque for terminal block screws may cause damage to the terminal block.
•
Tighten the fixing screw of the terminal block cover to a torque of 0.19 to 0.21 N·m (M3).
•
If you are connecting an External Regeneration Resistor, set the Regeneration Resistor
Selection servo parameter object (3016 hex).
•
Do not connect any External Regeneration Resistors between B1 and NC.
R
88
D-KN30H-ECT-L/-KN50H-ECT-L
Symbol
Name
Function
L1
Main circuit power supply
input
3-phase 200 to 230 VAC (170 to 253 VAC) 50/60 Hz
L2
L3
L1C
Control circuit power
supply input
Single-phase 200 to 230 VAC (170 to 253 VAC) 50/60 Hz
L2C
B1
External Regeneration
Resistor connection
terminals
*1
Normally short B2 and B3. If there is high regenerative energy, remove the
short-circuit bar between B2 and B3 and connect an External
Regeneration Resistor between B1 and B2.
B3
B2
NC
Do not connect.
U
Motor connection
terminals
Phase U These are the output terminals to the Linear Motor.
Be sure to wire them correctly.
V
Phase V
W
Phase W
Frame ground
This is the ground terminal. Ground to 100
or less.