![background image](http://html1.mh-extra.com/html/omron/r88d-kn-series/r88d-kn-series_user-manual_742799525.webp)
A-125
Appendicies
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
A
-3 Sysm
ac Err
o
r Sta
tus
Cod
es
App
A-3
-2 Error D
escr
iption
Event name
Servo Drive Overheat
Event code
34E10000 hex
Meaning
The temperature of the Servo Drive radiator or power elements exceeded the specified value.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
Continuously
Error attributes
Level
Minor fault
Recovery
Error reset (after
cycling slave
power)
Log category
System
Effects
User program
Continues.
Operation
Power drive circuit is OFF for relevant slave.
Indicators
EtherNet/IP NET RUN
EtherNet/IP NET ERR
EtherNet/IP LINK/ACT
---
---
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Remedy
Prevention
The ambient temperature of the
Servo Drive exceeded the specified
value.
Improve the ambient temperature and
the cooling conditions of the Servo
Drive.
Check the ambient temperature of the
Servo Drive and set up the necessary
cooling conditions.
Overload
Increase the capacities of the Servo
Drive and the motor. Or, increase the
setting of the acceleration/
deceleration time and lighten the
load.
Increase the setting of the
acceleration/deceleration time and
lighten the load as much as possible.
Attached
information
None
Precautions/
Remarks
“
15
”
is displayed on the Servo Drive front panel and F015 is given as the AlarmCode (4001 hex)