231
-
Rack Power Limit
Specify the upper limit of power consumption in rack maximum power consumption
management. If you select "No Limit", "0" is specified for this item and no limit is
imposed to power consumption. The default setting is "Unlimited" (0 watt). This item can
be edited only when the Blade Enclosure Inter Connect feature is enabled. The setting of
this item is distributed to EM cards on every Blade Enclosure being connected. Therefore,
you need to connect LAN cables and enable the Blade Enclosure Inter Connect feature on
all the Blade Enclosures before setting this item.
NOTES:
Maximum power consumption management is not available when
using automatic CPU blade boot after UPS power recovery.
If "Rack Power Limit" is assigned, power is distributed to each
Blade Enclosure in the rack based on the limit value. Initially, the
amount of power for each enclosure is the same. The rate then
changes depending on the operating status of each enclosure.
Blade Enclosure Inter Connect Timeout
In rack maximum power consumption management, specify the wait time for response
from the Blade Enclosures being linked. The default setting is "300" seconds. Use this
value in usual operation.