- 70 -
CFG_UPS_SET_COMMUNITY_NAME
Specify the community name for SNMP Set request issued to UPSs. The default setting is
"private."
CFG_UPSn_SERIAL_NUMBER, CFG_UPSn_CAPACITY
The serial numbers and power capacities [W] of up to four UPSs can be specified. The
default settings are blank characters and "0" [W]. In general, you may not specify these
values.
CFG_UPS_USE_STATIC_IP
Specify whether to enable or disable the UPS management using an IP address directly
assigned to UPS, not by the DHCP of EM card.
1: TRUE (enable)
0: FALSE (disable)
The default setting is "0" (disable).
To enable this feature, enter the IP address assigned to UPS in the following fields to
make EM card recognize the IP address of UPS.
CFG_UPS_STATIC_IPn (n: 1 to 4)
This setting is required to let EM card recognize the IP address directly assigned to UPS
when enabling the UPS management feature using the IP address directly assigned to
UPS.
EM card does not assign an IP address to UPS by using this address.
CFG_UPS_SVB_BOOT
If the number of healthy UPSs is less than the number of UPSs required for system
operation, specify whether to enable or disable the feature to reboot the CPU blade that
has been shutdown by the EM card when the input power to UPS is recovered.
1: TRUE (enable)
0: FALSE (disable)
The default setting is "0" (disable).
CFG_UPS_SHUTOFF_DELAY
Specify the time until the UPS actually enters into sleep state after the sleep command is
issued to UPS, in the unit of second.
If an illegal value is specified for the relevant UPS, the value longer than the specified
time and nearest to the allowable time is set to UPS.
The default setting is 90 seconds.