6.6.4 Control mode of fan
When So-26=0, and when radiator temperature reaches to setting temperature, fan starts running. When
radiator temperature is lower than So-27-5°, fan wills stop running.
When So-26=2, fan will run when servo ON or temperature is higher than 45°. When servo off and
radiator temperature is lower than 40°, fan will stop running after 500ms.
6.6.5 Parameter copy
8
Given command pulse numbers
display low 5 digits.
27
AI1 voltage
9
Given command pulse error
numbers
28
AI2 voltage
10
Given speed
29
Combined deviation
11
Given torque
30
Close-loop feedback
12
Analog speed command display
31
Gantry synchronous deviation
13
Analog torque command display
32
Reserved
14
D18~D15 status display
33
Hight- speed counter 1
15
D14~D11status display
34
Hight- speed counter 2
16
Other output interface status
display
35
PLC monitor
17
D4~D1 status display
36
Motor temperature
18
Drive current temperature
display
37
Motor shaft position
So-26
Fan control
speed position torque
Setting range
Setting unit
Mfr’s value
When enabled
0~2
N/A
2
Effective
Immediately
0: Fan is controlled by temperature.
1: Fan will run after power on.
2: Fan will run when servo drive starts running.
So-27
Fan temperature setting
speed position torque
Setting range
Setting unit
Mfr’s value
When enabled
10~100
°C
45
Effective
Immediately
So-44
Parameter copy
speed position torque
Summary of Contents for SD20-G Series
Page 35: ...SD20 G Series 35 M3 structure Fig 3 1 5 Servo drive structure 3...
Page 36: ...SD20 G Series 36 ML3 structure 118 5 5 7 5 93 297 8 223 118 93 0 5 12 5 7 5 4 M4...
Page 38: ...SD20 G Series 38 M4 structure Approx mass 10 365 kg Fig 3 1 7 Servo drive structure 5...
Page 39: ...SD20 G Series 39 M5 structure Approx msaa 11 1Kg Fig 3 1 8 Servo drive structure 6...
Page 40: ...SD20 G Series 40 M6 structure Approx mass 17 4Kg Fig 3 1 9 Servo drive structure 7...
Page 182: ...SD20 G Series 182 Fig 6 4 44SD20E Cam internal frameworkdiagram...