C A B A N D BO DY M O U N T IN G S 1-67
T E S T R E A D I N G S
Ambient Air in Degrees F. (In Auxiliary
Fan Air Blast 2" Ahead of Condenser).
70
80
90
100
110
Air Quality
Arid
Humid
Arid
Humid
Arid
Humid
Arid
Humid
Arid
Humid
Average Compressor Head
P re ssu re -P S 1
125/155
150/180
160/190
180/210
197/227
213/243
225/255
250/280
270/300
290/320
Average Suction Throttling Valve
Pressure—PSI
20/23
21/24
20/23
22/25
21/24
25/28
24/27
29/32
28/31
36/39
Center Outlet Temperature Degree F.
41/44
48/52
44/48
53/57
48/52
58/62
52/57
62/68
58/65
68/75
Shown in the above table are the average readings expected in arid or dry air, and in humid or moist air with maximum allowable tolerance
shown.
Humid air is considered 2 0 -9 0 % R.H. Nozzle
Arid air is considered 5—20% R.H. Nozzle
Figure 11 — Operational Test Data Chart
provide an internal pressure at slightly above
atmospheric pressure.
A SSEM B LY
1. All precautions should be taken to prevent
damage to fittings or connections. Even minute
damage to a connection could cause it to leak.
2. Any fittings getting grease or dirt on them
should be wiped clean with a cloth dampened with
alcohol. Do not use chlorinated solvents such as
trichloroethylene for a cleaning agent, as they are
contaminants. If dirt, grease or moisture gets in
side the hoses and cannot be removed, the hose
should be replaced.
3. Sealing caps should be removed from sub-
assemblies just prior to making connections for
final assembly.
4. Use a small amount of clean refrigeration
oil (525 or 1000 viscosity) on all tube and hose
joints, and dip the O-ring gasket (when used) in
this oil before assembling the joint, as this oil will
help in making a leak-proof joint.
5. Do not connect the receiver-dehydrator as
sembly until all other sealed sub-assemblies have
been connected. This is necessary to insure opti
m um dehydration and maximum moisture protec
tion of the refrigeration system.
C A U T IO N - LIQUID IN D IC A T O R (SIGHT GLASS)
Under normal conditions, the receiver-dehy
drator will show clear with about 3 pounds of re
frigerant in the system. However, the air condi
tioner will not produce its best performance until
3-1/4 pounds of refrigerant are in the system. Do
not overcharge with refrigerant, as this will result
in extremely high head pressures and the com
pressor safety valve will "blow."
PERFORMANCE TESTING
In order to determine if an air conditioning
system is operating properly and efficiently, it must
be performance tested. The first step to diagnosing
a system that has been malfunctioning should be a
complete performance test (see fig. 11).
Correct pressures indicate that the required
charge of refrigerant is in the system and that it
is functioning properly.
CHEVROLET SERIES 70-80 H EAVY DUTY TRUCK SH O P M A N U A L
Summary of Contents for 70 1969 Series
Page 1: ...CHEVROLET HEAVY DUTY TRUCK SHOP MANUAL...
Page 3: ......
Page 11: ...LUBRICATION 0 4 CHEVROLET SERIES 70 80 HEAVY DUTY TRUCK SHOP MANUAL...
Page 27: ......
Page 119: ......
Page 361: ......
Page 371: ......
Page 427: ......
Page 443: ......
Page 451: ......
Page 493: ......
Page 499: ......
Page 549: ......
Page 555: ......
Page 609: ......
Page 715: ...am...
Page 745: ......
Page 910: ......
Page 913: ......