13.15
Configuring the RSL Threshold Alarm (CLI)
You can enable an alarm to be triggered in the event that the RSL falls beneath a
defined threshold. This alarm is alarm ID 1610,
Radio Receive Signal Level is below
the configured threshold
. By default, the alarm is disabled.
To enable the RSL threshold alarm, enter the following command in radio view:
radio[x/x]> rf rsl-degradation set admin enable
To disable the RSL threshold alarm, enter the following command in radio view:
radio[x/x]> rf rsl-degradation set admin disable
To set the threshold of the RSL threshold alarm, enter the following command in
radio view:
radio[x/x]> rf rsl-degradation set threshold <-99-0>
The default threshold is -68 dBm.
To display the current alarm configuration, enter the following command in radio
view:
radio[x/x]> rf rsl-degradation show status
The following commands enable the RSL threshold alarm for radio carrier 1 and
set the threshold to -55 dBm.
root> radio slot 2 port 1
radio [2/1]>rf rsl-degradation set admin enable
radio [2/1]>rf rsl-degradation set threshold -55
radio [2/1]>rf rsl-degradation show status
RSL degradation alarm admin: enable
RSL degradation threshold: -55
radio [2/1]>
The alarm is cleared when the RSL goes above the configured threshold. The
alarm is masked if the radio interface is disabled, the radio does not exist, or a
communication-failure alarm (Alarm ID #1703) is raised.