APPENDIX
App. - 15
App. 4.6 Maintenance and service
WARNING
To avoid an electric shock, only qualified personnel should attempt inspections.
For repair and parts replacement, contact your local sales office.
App. 4.6.1 Inspection items
It is recommended that the following points periodically be checked.
(1) Check for loose terminal block screws. Retighten any loose screws.(Except for MR-J4-03A6 and MR-
J4W2-0303B6)
Servo amplifier
Tightening
torque
[N•m]
L1 L2 L3 N- P3 P4 P+ C D L11 L21 U V W PE
MR-J4-10_(1)/MR-J4-20_(1)/
MR-J4-40_(1)/MR-J4-60_(4)/
MR-J4-70_/MR-J4-100_(4)/
MR-J4-200_(4)/MR-J4-350_(4)
1.2
MR-J4-500_
1.2
0.8 1.2
MR-J4-700_(4)/MR-J4-500_4
1.2 0.8 1.2
MR-J4-11K_(4)/MR-J4-15K_(4)
3.0 1.2
3.0
MR-J4-22K_(4)
6.0 1.2 6.0
MR-J4W_-_B
1.2
(2) Servo motor bearings, brake section, etc. for unusual noise.
(3) Check the cables and the like for scratches or cracks. Perform periodic inspection according to
operating conditions.
(4) Check that the connectors are securely connected to the servo motor.
(5) Check that the wires are not coming out from the connector.
(6) Check for dust accumulation on the servo amplifier.
(7) Check for unusual noise generated from the servo amplifier.
(8) Check the servo motor shaft and coupling for connection.
(9) Make sure that the emergency stop circuit operates properly such that an operation can be stopped
immediately and a power is shut off by the emergency stop switch.
Summary of Contents for MR-J4W2-0303B6
Page 39: ...2 INSTALLATION 2 8 MEMO ...
Page 97: ...4 STARTUP 4 20 MEMO ...
Page 181: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Page 235: ...9 DIMENSIONS 9 6 MEMO ...
Page 245: ...10 CHARACTERISTICS 10 10 MEMO ...
Page 309: ...13 USING STO FUNCTION 13 14 MEMO ...
Page 365: ...15 USING A DIRECT DRIVE MOTOR 15 24 MEMO ...
Page 389: ...16 FULLY CLOSED LOOP SYSTEM 16 24 MEMO ...
Page 461: ...17 APPLICATION OF FUNCTIONS 17 72 MEMO ...
Page 556: ...APPENDIX App 41 ...
Page 585: ...MEMO ...