17. APPLICATION OF FUNCTIONS
17 - 36
5) If an error occurs
If a tuning error occurs during tuning, one-touch tuning will be stopped. With that, the following
error code will be displayed in status. Check the cause of tuning error. When executing one-touch
tuning again, stop the servo motor once. In addition, after returning the moving part to the tuning
start position, execute it.
Display
Name
Error detail
Corrective action example
C000
Tuning canceled
"Stop" was clicked during one-touch tuning.
C001
Overshoot exceeded
Overshoot amount is a value larger than the
one set in [Pr. PA10 In-position range] and
[Pr. PX14 One-touch tuning - Overshoot
permissible level].
Increase the in-position range or overshoot
permissible level.
C002
Servo-off during tuning
The one-touch tuning was attempted in the
user command method during servo-off.
The servo amplifier will be servo-off status
during one-touch tuning.
When executing one-touch tuning in the user
command method, turn to servo-on, and then
execute it.
Prevent the servo amplifier from being the
servo-off status during one-touch tuning.
C003
Control mode error
1. The one-touch tuning was attempted while
the torque control mode was selected in
the control modes.
Select the position control mode or speed
control mode for the control mode from the
controller, and then execute one-touch tuning.
Do not change the control mode during the
one-touch tuning.
2. During one-touch tuning, the control mode
was attempted to change from the position
control mode to the speed control mode.
C004
Time-out
1. One cycle time during the operation has
been over 30 s.
Set one cycle time during the operation (time
from the command start to the next command
start) to 30 s or less.
2. The command speed is slow.
Set the servo motor speed to 100 r/min or
higher. Error is less likely to occur as the
setting speed is higher.
When one-touch tuning by the amplifier
command is used, set a permissible travel
distance so that the servo motor speed is 100
r/min or higher. Set a permissible travel
distance to two or more revolutions as a guide
value to set the servo motor speed to 100
r/min.
3. The operation interval of the continuous
operation is short.
Set the stop interval during operation to 200
ms or more. Error is less likely to occur as the
setting time is longer.
C005
Load to motor inertia
ratio misestimated
1. The estimation of the load to motor inertia
ratio at one-touch tuning was a failure.
Drive the motor with meeting conditions as
follows.
The acceleration time constant/deceleration
time constant to reach 2000 r/min (mm/s) is
5 s or less.
Speed is 150 r/min (mm/s) or higher.
The load to servo motor (mass of linear
servo motor's primary side or direct drive
motor) inertia ratio is 100 times or less.
The acceleration/deceleration torque is
10% or more of the rated torque.
2. The load to motor inertia ratio was not
estimated due to an oscillation or other
influences.
Set to the auto tuning mode that does not
estimate the load to motor inertia ratio as
follows, and then execute the one-touch
tuning.
Select "Auto tuning mode 2 (_ _ _ 2)",
"Manual mode (_ _ _ 3)", or "2 gain
adjustment mode 2 (_ _ _ 4)" of "Gain
adjustment mode selection" in [Pr. PA08].
Manually set [Pr. PB06 Load to motor
inertia ratio/load to motor mass ratio]
properly.
Summary of Contents for MR-J4W2-0303B6
Page 39: ...2 INSTALLATION 2 8 MEMO ...
Page 97: ...4 STARTUP 4 20 MEMO ...
Page 181: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Page 235: ...9 DIMENSIONS 9 6 MEMO ...
Page 245: ...10 CHARACTERISTICS 10 10 MEMO ...
Page 309: ...13 USING STO FUNCTION 13 14 MEMO ...
Page 365: ...15 USING A DIRECT DRIVE MOTOR 15 24 MEMO ...
Page 389: ...16 FULLY CLOSED LOOP SYSTEM 16 24 MEMO ...
Page 461: ...17 APPLICATION OF FUNCTIONS 17 72 MEMO ...
Page 556: ...APPENDIX App 41 ...
Page 585: ...MEMO ...