10. CHARACTERISTICS
10 - 9
10.4 Cable bending life
The bending life of the cables is shown below. This graph calculated values. Since they are not guaranteed
values, provide a little allowance for these values.
10.5 Inrush currents at power-on of main circuit and control circuit
POINT
For a servo amplifier of 600 W or less, the inrush current values can change
depending on frequency of turning on/off the power and ambient temperature.
Since large inrush currents flow in the power supplies, always use molded-case circuit breakers and
magnetic contactors. (Refer to section 11.6.)
When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an
inrush current, be used.
The following table indicates the inrush currents (reference data) that will flow when 240 V AC is applied at
the power supply capacity of 2500 kVA and the wiring length of 1 m. Even when you use a 1-phase 200 V
AC power supply with MR-J4W2-22B to MR-J4W2-77B, MR-J4W3-222B, and MR-J4W3-444B, the inrush
currents of the main circuit power supply is the same.
MR-J4
2-axis servo amplifier
MR-J4
3-axis servo amplifier
Inrush currents (A
0-P
)
Main circuit power supply (L1/L2/L3)
Control circuit power supply (L11/L21)
MR-J4W2-22B MR-J4W3-222B
113 A
(attenuated to approx. 6 A in 20 ms)
24 A
(attenuated to approx. 2 A in 20 ms)
MR-J4W2-44B MR-J4W3-444B
MR-J4W2-77B
113 A
(attenuated to approx. 11A in 20 ms)
MR-J4W2-1010B
Summary of Contents for MR-J4W2-0303B6
Page 39: ...2 INSTALLATION 2 8 MEMO ...
Page 97: ...4 STARTUP 4 20 MEMO ...
Page 181: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Page 235: ...9 DIMENSIONS 9 6 MEMO ...
Page 245: ...10 CHARACTERISTICS 10 10 MEMO ...
Page 309: ...13 USING STO FUNCTION 13 14 MEMO ...
Page 365: ...15 USING A DIRECT DRIVE MOTOR 15 24 MEMO ...
Page 389: ...16 FULLY CLOSED LOOP SYSTEM 16 24 MEMO ...
Page 461: ...17 APPLICATION OF FUNCTIONS 17 72 MEMO ...
Page 556: ...APPENDIX App 41 ...
Page 585: ...MEMO ...