Ver.3
−
−
−
−
39
(2)
Writing Holing Register[06h]
、
target register: External register
Query:
No
Field Name
Example
(Hex)
1
Slave address
01
2
Function code
06
3
Register start address
(high order)
12
4
Register start address
(low order)
00
5
Change data (high order)
00
6
Change data (low order)
50
7
CRC-16 (high order)
8C
8
CRC-16 (low order)
8E
Response:
After Modbus communication above, 80% is written as
[O] input active range end voltage (A014)
No
Field Name
Example
(Hex)
1
Slave address
01
2
Function code
06
3
Register start address
(high order)
12
4
Register start address
(low order)
00
5
Change data (high order)
00
6
Change data (low order)
50
7
CRC-16 (high order)
8C
8
CRC-16 (low order)
8E
Register address value = Register
Number - 1
0050h→80d→80%
Register address value = Register
Number - 1
0050h→80d→80%